CS15-L Current Transducer
Services Available
Repair No
Calibration No
Free Support No

Visão Geral

The CS15 is a modified version of the CS10 Current Transducer developed specifically for our CR200(X)-series dataloggers. It monitors ac current along an electrical wire for the range of 0.15 A to 125 A.

Leia mais

Benefícios e Características

  • Ideal applications include motor or generator load conditions, efficiency studies, intermittent fault detection, and rough submetering
  • No direct electrical connection to the electrical system

imagens

Descrição Técnica

The CS15 detects the ac current along an electrical wire using the magnetic field that is generated by that current. It is external to the wire jacket and has no direct electrical connection to the system. This transducer outputs a millivolt signal that our CR200(X)-series dataloggers can directly measure.

The CS15 can be used for motor or generator load condition monitoring, efficiency studies, intermittent fault detection, and rough submetering.

Especificações

Measurement Range 0.15 to 125 A
Frequency 50 and 60 Hz
Insulation Resistance 100 MΩ (@ 500 Vdc)
High Potential 2000 V
Rated Current 125 A
Accuracy with 10 Ω Maximum Burden (resistive) Typically ±5% of actual value (with provided multiplier)
Operating Temperature Range -25° to +55°C
Case Material Polypropylene resin
Construction Epoxy encapsulated
Outer Diameter 4.8 cm (1.89 in.)
Inner Diameter 1.9 cm (0.75 in.)
Height 1.7 cm (0.67 in.)

Documentos Relacionados

Compatibilidade

Data Logger Considerations

The CS15 was designed specifically for the CR200(X)-series dataloggers. It is measured with the VoltSE instruction. The measurement is generally taken repeatedly inside a measurement loop, then the RMS (root-mean-square) value is determined.

Perguntas Frequentes Relacionadas

Number of FAQs related to CS15-L: 2

  1. Yes, by connecting the red wire to ground rather than its normal location.
  2. Not directly. If the CS15-L is connected to a CR200(X) datalogger, the data logger can take the ac measurement and control a solid-state relay based on some threshold within the data logger program. The solid-state relay can then control other relays, solenoids, or motor starters. (Use of a solid-state relay is preferred because the data logger can trigger it with a small 5 Vdc mA signal.) For more information, see the “Measurement and Control Peripherals” section of the operator’s manual.