4WPB1K 1-kohm, Four-Wire PRT Bridge Terminal Input Module

Visão Geral

The 4WPB1K provides completion resistors to enable your Campbell Scientific data logger to measure 1000-ohm platinum resistive thermometers (PRT).using the half-bridge four-wire measurement method.

Leia mais

Benefícios e Características

  • Provides high-accuracy completion resistor and convenient wiring for four-wire, 1000-ohm PRT measurements
  • Easy to install or remove
  • Connects directly into data logger input terminals
  • Compatible with most Campbell Scientific data loggers

imagens


3D / CAD Files:

Descrição Técnica

4-Wire PRT Bridge Module Schematic
(Rf=1 kΩ for the 4WPB1K)

4WPB1K-to-Sensor Hookup

Especificações

Used With 1 kΩ platinum resistive thermometer (PRT)
Dimensions 1.5 x 1.5 x 2.7 cm (0.6 x 0.6 x 1.0 in.) for body with prongs
Weight 6 g (0.2 oz)

Current Limiting

Resistance 10 kΩ
Tolerance ±5% (@ 25°C)
Power Rating 0.25 W

Completion Resistor (bulk metal foil)

Resistance 1 kΩ
Tolerance ±0.01% (@ 25°C)
Maximum Temperature Coefficient ±0.8 ppm/°C
Power Rating 0.25 W (@ 70°C)

Compatibilidade

Please note: The following shows notable compatibility information. It is not a comprehensive list of all compatible products.

Data Loggers

Product Compatible Note
21X (retired)
CR10 (retired)
CR1000 (retired)
CR1000X
CR10X (retired)
CR200X (retired)
CR206X (retired)
CR211X (retired)
CR216X (retired)
CR23X (retired)
CR295X (retired)
CR300
CR3000 (retired)
CR310
CR350
CR500 (retired)
CR5000 (retired)
CR510 (retired)
CR6
CR800 (retired)
CR850 (retired)
CR9000 (retired)
CR9000X (retired)

Measurement and Control

Product Compatible Note
Granite Volt 108
Granite Volt 116

Additional Compatibility Information

Data Logger Considerations

The 4WPB1K consumes two adjacent differential analog inputs; the first channel requires an adjacent analog ground channel to accept the "ground prong" of the 4WPB1K. Not all data logger terminal strips have this sequence on all channels, so please check your data logger's wiring panel to confirm channel assignments, especially if you plan to use multiple terminal input modules.

Newer CR10X Wiring Panels and the CR10XTCR Thermocouple Cover are deep enough to cover the data logger input channels with a terminal input module attached; older CR10TCRs are not deep enough.

Programming

When using CRBasic, the 4WPB1K is measured with the BrHalf4W Instruction followed by the PRT Instruction. When using Edlog, the 4WPB1K is measured with Instruction 9 (Full Bridge w/ Measured Compensation) followed by Instruction 16 (Temperature RTD).

Perguntas Frequentes Relacionadas

Number of FAQs related to 4WPB1K: 1

  1. The 4WPB100, 4WPB1K, and 4WHB10K terminal input modules can be used instead of the 3WHB10K module. However, ensure that the jumper is installed between the ground side of the sensor and the low input of the second channel to maintain the four-wire accuracy.